LC Series Oval Gear Flowmeter: Models, Flow Ranges, Wiring and Fault Table

Table of Content [Hide]

    LC Series oval gear flowmeter manual


    This is the LC Series manual as a page instead of a file. The same content, the tables as real tables, so the model codes, the flow range for your viscosity and the pulse equivalent for your counter are searchable and copyable — and so a typo in the field can be checked without downloading a PDF and scrolling to page nine.

    What this page covers: how the eight model codes differ (body material and viscosity class), the flow range for every bore from DN10 to DN200 across four viscosity bands, the accuracy and pressure classes, the transmitter and wiring options including the pulse equivalent table, the LB07 4–20 mA settings, the installation rules that decide whether the meter reads right, and the fault table from section XI.

    Revision: based on the LC Series manual, dossier 20260731. The original PDF is linked at the end.

    The Eight Model Codes: Two Variables, Not Eight Products

    There are not eight instruments here. There are two choices — what the body is made of, and whether the meter is built for ordinary or high-viscosity liquid — plus a temperature variant of each.

    Name

    Iron casting

    Cast steel

    High-temp iron casting

    High-temp cast steel

    High-viscosity iron casting

    High-viscosity cast steel

    Stainless steel

    Transmitter

    Model

    LC-A

    LC-E

    LC-TA

    LC-TE

    LC-NA

    LC-NE

    LC-B

    LC-13

    Body

    iron casting

    cast steel

    iron casting

    cast steel

    iron casting

    cast steel

    stainless steel

    various

    Gears

    iron casting

    iron casting

    iron casting

    iron casting

    iron casting

    iron casting

    stainless steel

    various

    Reading the table:

    • LC-A and LC-E are the general-purpose pair. Choose between them on pressure and on the corrosion question, not on flow range — the ranges are the same.

    • LC-TA and LC-TE are the same bodies with a radiator between the transmitter and the counting mechanism. That is what extends the working temperature to 200 °C on the pointer version.

    • LC-NA and LC-NE are the high-viscosity pair. The measuring chamber and gearing tolerate liquids up to 2000 mPa·s, which the general-purpose models do not cover.

    • LC-B is the stainless steel version, and the manual is explicit about when to take it: if the tested liquid is chemically corrosive, a flowmeter of stainless steel should be selected.

    • LC-13 is not a body at all — it is the transmitter option, covered below.

    Function Codes: What the Counter Adds

    The suffix after the model is the counter and output configuration. It decides what you can read at the meter, and whether you need a separate transmitter at all.

    Function

    A1

    A

    Z

    13

    J1

    ELZ

    Pointer, cumulative six rollers

    ●

    ●





    Pointer, cumulative six rollers, resettable

    ●

    ●

    ●




    Pointer, with message

    ●




    ●


    Single message (signal output)




    ●



    LCD display — instantaneous, cumulative, 4–20 mA, pulse, RS485






    ●

    In practice:

    • A1 / A / Z are mechanical pointer counters. Z adds a reset. If the installation is a filling point where the operator zeroes between batches, this is the one.

    • 13 gives a signal output only.

    • J1 is the pointer counter with a message function.

    • ELZ is the LCD version carrying instantaneous flow, cumulative total, 4–20 mA, pulse and RS485 in one head. For anything that has to reach a PLC or a batch controller, this is the code to specify, and it removes the need for a separate LC-13 transmitter.

    Flow Range by Bore and Viscosity

    This is the table most enquiries get wrong. The same bore measures a different range depending on how thick the liquid is, and the high-viscosity models are not simply the same numbers shifted.

    Standard and high-temperature models (LC-A / LC-E / LC-TA / LC-TE), accuracy class 0.5, flow in m³/h:

    DN (mm)

    Viscosity 0.6–2 mPa·s

    Viscosity 2–200 mPa·s

    10

    0.2 – 0.4

    0.08 – 0.4

    15

    0.6 – 1.5

    0.3 – 1.5

    20

    0.8 – 3

    0.6 – 3

    25

    1.2 – 6

    0.8 – 6

    40

    5 – 15

    3 – 15

    50

    6 – 24

    4 – 24

    65

    10 – 40

    8 – 40

    80 (light)

    10 – 40

    8 – 40

    80 (heavy)

    15 – 60

    10 – 60

    100

    30 – 100

    15 – 100

    150

    45 – 190

    34 – 190

    200

    68 – 340

    56 – 340

    High-viscosity models (LC-NA / LC-NE / LC-NB), accuracy class 0.5, flow in m³/h:

    DN (mm)

    Viscosity 200–1000 mPa·s

    Viscosity 1000–2000 mPa·s

    10

    0.04 – 0.3

    0.03 – 0.2

    15

    0.2 – 1.0

    0.1 – 0.7

    20

    0.4 – 2.1

    0.25 – 1.5

    25

    0.6 – 4.2

    0.6 – 3

    40

    2.1 – 10.5

    1.0 – 7.5

    50

    2.4 – 16.8

    2 – 12

    65

    6 – 28

    4 – 20

    80 (light)

    6 – 28

    4 – 20

    80 (heavy)

    8 – 42

    6 – 30

    100

    10 – 70

    10 – 50

    150

    27 – 133

    19 – 95

    200

    48 – 238

    34 – 170

    Three things worth noticing:

    1. Thicker liquid lowers the minimum, not the maximum. On DN25 the top end is 6 m³/h either way, but the bottom moves from 1.2 to 0.8 m³/h between the thin and thick columns. That is the volumetric-efficiency effect: a slow-turning gear with viscous liquid seals better than a slow-turning gear with water.

    2. DN50 and DN80 come in light and heavy types. The heavy type has a larger range at the same bore, so "DN80" alone is not a specification.

    3. The 0.2 % class has its own range table. Those numbers differ from the 0.5 % table above and are printed separately in the manual. Do not size from this page if you are ordering the high-precision version.

    Read these tables as a shortlist, not a specification — confirm the bore against your minimum and maximum flow before ordering.

    Accuracy, Pressure and Temperature

    Property

    LC-A

    LC-E

    LC-B

    Nominal pressure

    1.6 MPa

    1.6 / 2.5 / 4.0 / 6.3 MPa

    1.6 / 2.5 / 4.0 / 6.3 MPa

    Accuracy

    0.5 % standard; 0.2 % high-precision version

    same

    same

    Temperature depends on the counter, not the body:

    Counter

    Temperature range

    Pointer, conventional

    −20 ~ +80 °C

    Pointer, high temperature

    −20 ~ +200 °C

    LCD, conventional

    −20 ~ +60 °C

    LCD, high temperature

    −20 ~ +150 °C

    So a 180 °C oil line needs two selections, not one: the TA or TE body and the high-temperature pointer counter. An LCD head on that line is only rated to 150 °C.

    The manual publishes an error and pressure-loss curve for the 0.5 class across four media — aviation gasoline at 0.7 mPa·s, water at 1 mPa·s, light diesel at 5 mPa·s and transformer oil at 20 mPa·s — with the error band held inside ±0.5 % and pressure loss rising with both flow and viscosity. If pressure loss matters on your line, read that curve before choosing the bore: it is the reason a small bore is not automatically the cheap answer.

    Transmitters and Outputs

    LC-13 transmitter — the body-and-transmitter combination for remote display, control and recording:

    Parameter

    Value

    Outputs

    MF: 4–20 mA; GF: photoelectric pulse

    Supply

    DC 12 V or DC 24 V

    Pipe connection

    flange JB/T79~82—1994

    Transmission distance

    0 – 1000 m

    Electrical accuracy

    ±1 pulse

    Ambient temperature

    −10 ~ +60 °C

    GF-IGF-II pulse transmitter — the standalone pulse head matched to the LC series:

    Parameter

    Value

    Supply

    DC 12 / 24 V

    Transmission distance

    0 – 1000 m

    Electrical accuracy

    ±1 pulse

    Ambient temperature

    −10 ~ +65 °C

    Explosion-proof grade

    ExdIIBT4

    Pulse equivalent: what to type into the counter

    If you are pairing the meter with an A1 or J1 counter, the pulse equivalent is fixed by bore — it is not a free parameter, and getting it wrong scales every total by a constant.

    DN (mm)

    L per pulse

    Pulses per second at full scale

    10

    0.004

    27.77

    15

    0.04

    10.41

    20

    0.04

    20.83

    25

    0.04

    41.67

    40

    0.4

    10.41

    50

    0.4

    16.67

    65 / 80 (light)

    0.4

    27.77

    80 (heavy)

    0.4

    41.67

    100

    0.4

    69.44

    150

    0.4

    52.78

    200

    0.4

    94.44

    Wiring: Two-Wire and Three-Wire 4–20 mA

    The transmitter head terminates on four numbered positions: 1: V+, 2: SO, 3: I+, 4: GND. Which of them you use depends on whether the loop is two-wire or three-wire.

    Mode

    Terminals used

    Wiring

    Two-wire 4–20 mA

    V+, GND

    V+ to 24 V positive; GND to the positive end of the loop

    Three-wire 4–20 mA

    V+, I+, GND

    V+ to 24 V positive; I+ to the current output positive; GND to the 24 V negative

    Two-wire and three-wire 4-20 mA wiring on the LC transmitter head

    Two-wire uses the supply pair as the signal pair; three-wire keeps the current output separate. The load goes in series in both cases.

    Setting the LB07 4–20 mA converter

    The LB07 head carries five parameters. They are reached with the two keys — M (left) and S (right) — and they are the whole commissioning procedure:

    Parameter

    Meaning

    Range

    P00

    Coefficient of flowmeter (pulse equivalent)

    0.00001 – 9.99999 L/pulse

    P01

    Maximum flow (range)

    m³/h, two decimals

    P02

    Minimum flow — sets the reset time

    m³/h, two decimals

    P03

    4 mA trim

    larger value, greater current

    P04

    20 mA trim

    larger value, greater current

    In the running state, long-press S to display P00 and its value, then short-press S to step to P01, P02 and so on. Short-press M to enter edit, S to increment, M to move to the next digit. To save, hold S until the display flashes "SaUEd" and returns to the running state — if you do not see SaUEd, nothing was written.

    While the accumulation is displayed, a short press of S resets the total. The manual notes this is the function used to adjust for pulse loss, which is worth knowing before someone presses it by accident.

    Installation: The Rules That Decide Whether It Reads Right

    These come from section IX of the manual, and most field complaints trace back to one of them.

    1. Fit the matching filter before the meter, outlet to the meter inlet, with the arrow on both bodies pointing with the flow.

    2. If the liquid carries gas, fit a gas elimination filter upstream. The manual treats this as a separate device, not a setting.

    3. The oval gears must sit horizontally — the dial disc perpendicular to the ground — whether the pipe runs horizontally or vertically. This is the rule most often broken on vertical runs.

    4. If the dial is awkward to read, rotate the counter 90° or 180°. It is designed to be turned.

    5. On a new meter, push the elliptical gear a few times from the outlet with a bamboo stick. If it does not move, soak in diesel. (Factory inspection can leave sediment.)

    6. A flow control valve at the inlet, an open/close valve at the outlet, and open slowly — sudden opening produces water hammer and a spike the gears will remember.

    7. Flush the new pipeline before fitting the meter, using a spool piece in its place, so welding slag and debris never reach the measuring chamber.

    8. Never test a cast iron or cast steel meter with water. This is stated flatly in the manual, and it is the reason the factory calibrates on diesel.

    9. Do not exceed the technical maximum flow — run at 50–80 % of it. At the top of the range the error curve opens up and the pressure loss is at its steepest.

    Error Calculation and Adjustment

    The basic error is calculated against a volumetric standard:

    E = (V_measured − V_actual) / V_actual × 100 %

    Where V_measured is the meter reading and V_actual is the standard after correction. A positive result means the meter runs fast; a negative result means it runs slow.

    The adjustment is mechanical, not electronic: a pair of adjusting gears in the counter changes the transmission ratio, which shifts the error curve into a new coordinate system. The standard pair is 38/35; the manual also references 41/38 and 40/37. Two cautions straight from the text:

    • Error adjustment cannot change the flow characteristics of the meter — it moves the curve, it does not flatten it.

    • If the error exceeds 1 %, replacing the gear pair is not the fix. At that point the double-layer gear is worn and should be replaced, then the meter recalibrated.

    Common Faults

    Reproduced from section XI. This is the part of the manual worth having on a phone in the plant rather than a laptop in the office.

    Fault

    Cause

    Action

    Oval gear does not rotate

    Debris in the pipeline; damaged filter letting solids into the chamber

    Remove the meter and the line, clean the chamber, repair or replace the filter

    Leakage at the axial sealing coupling

    Packing worn or dry

    Tighten the gland or replace the packing, refill sealing oil

    Pointer rotation unstable

    Loose pointer or washer; stiff rotating parts

    Retighten, free the rotating parts

    Small-flow error too negative

    Elliptical gear catching the chamber wall — bearing wear or chamber deformation

    Replace bearings, repair the chamber and gear, ensure clearance, calibrate after repair

    Error changes a lot

    Large flow pulsation, or gas in the liquid

    Reduce pulsation, add a gas separator

    Error too large but within ±1 %

    Clearance changed after service

    Recalibrate and adjust

    No signal when transmitting

    Transmitting block position wrong; polarity reversed

    Move the block left/right; rewire — + to the red wire, − to the black wire

    On a 0.2 level meter the manual adds a tolerance note: after service, the change between maximum and minimum should not exceed ±0.17 %.

    What to Send When Ordering

    The manual's ordering list, condensed to what actually decides the build:

    1. Model, specification and material — or the liquid, and let the material follow.

    2. Medium temperature, working pressure and flow range.

    3. Medium viscosity, or the medium name if the viscosity is unknown. This is the one that changes the model family.

    4. Special requirements — remote transmission, explosion protection.

    5. Flange standard, if it is not JB/T79~82—1994.

    If the viscosity is missing, the quotation will be a guess between two different products.

    Download the Original Manual

    LC Series Oval Gear Flowmeter — instruction manual (PDF)

    Two notes from section XII that are easy to miss: the instrument is tested with diesel before dispatch according to JJG667-2010 Liquid Volumetric Flowmeter, and the matching filter is an independent product priced separately — it is not part of the meter.

    FAQ

    What is the difference between LC-A, LC-E and LC-B? Body and gear material. LC-A is iron casting at 1.6 MPa; LC-E is cast steel available to 1.6, 2.5, 4.0 and 6.3 MPa; LC-B is stainless steel, which the manual specifies for chemically corrosive liquids. Their flow ranges are the same for a given bore.

    What does the ELZ code mean? The LCD counter configuration: instantaneous flow, cumulative total, 4–20 mA, pulse and RS485 in one head. Specifying ELZ removes the need for a separate LC-13 transmitter.

    Why does the manual say not to test the meter with water? Because cast iron and cast steel bodies and gears corrode. The factory calibration is done on diesel under JJG667-2010, and a water test on a carbon steel meter leaves the chamber rusting before it is ever installed.

    Which flow range applies to DN25 with 500 mPa·s oil? Use the high-viscosity table: DN25 spans 0.6–4.2 m³/h in the 200–1000 mPa·s band. The general-purpose table does not cover 500 mPa·s at all, so the model family changes, not just the bore.

    My reading is low at small flow — what is worn? The manual's diagnosis is that the elliptical gear is catching the chamber wall, from bearing wear or a deformed measuring cavity. Replace the bearings, repair the chamber and gear, confirm the clearance, then recalibrate. Do not correct it with the adjusting gears.

    Where in the range should the meter normally run? Between 50 % and 80 % of maximum flow. At the top of the range the error curve opens out and pressure loss is steepest; at the bottom the gear turns too slowly for the viscosity to seal the clearances.

    References

    • LC Series Oval Gear Flowmeter instruction manual, sections II–XIII.

    • JJG667-2010, Liquid Volumetric Flowmeter — the verification regulation the factory tests against.

    • JB/T79~82—1994 — flange standard used on the LC-13 transmitter connection.

    If you are selecting between the general-purpose and high-viscosity families and the viscosity figure is uncertain, send the medium name and the temperature and we will come back with the family first, the bore second.

    Ethan Liu
    Ethan Liu

    Ethan Liu is JUJEA's technical content specialist, translating complex sensor integration and industrial automation concepts into practical insights for engineers, system integrators, procurement professionals, and decision-makers worldwide.

    We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. Part of the tracking is necessary to ensure SEO effectiveness,
    By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.
    Reject Accept