The MF series is not one flow meter with six options. It is six products that happen to share a sensor family, and they answer six different questions. Two of them are meters. Two of them are controllers with a valve inside. One is built for litres per hour, another for standard cubic centimetres per minute. Picking the wrong one is not a small mistake — it usually shows up as a range that never gets above 30% of scale, or a controller that cannot hold setpoint because the supply pressure is below its differential window.
There is a second trap that catches even experienced buyers, and it is buried in a footnote: every flow range in the selection guide is calibrated on air. Measuring argon, propane or carbon dioxide on an air-calibrated meter does not give you the same span. The conversion table in the manual puts propane at 34.59% of the air range. A meter bought as a 1000 L/min air unit is a roughly 346 L/min propane unit.
This guide covers what actually differs across MF30, MF50, MF51, MF52, MF60 and MF61 — the ranges, the accuracy classes, the units, the power requirements, the connectors and the gas conversion — so the model code you order matches the gas you are measuring.
Work through these before looking at a model number. Each one eliminates series quickly.
| Question | What it eliminates |
|---|---|
| What is the flow, in what unit? | L/min, Nm³/h, NmL/min and SCCM/SLPM are four different families — not interchangeable |
| Do you need to measure, or to control? | MF60 and MF61 contain a normally-closed valve and accept a setpoint; the others only measure |
| What accuracy does the application justify? | ±1.0% FS (MF60) versus ±(1.5+0.2FS)% (MF50, MF51) versus ±(2.0+0.2FS)% (MF30) |
| What wetted material? | Anodised aluminium, 304 or 316 body — a corrosive or high-purity gas removes F0 |
| Which gas, exactly? | Determines the calibration digit in the model code and the usable span |
The unit question is the one that most often goes wrong in an enquiry. "Ten litres a minute" and "ten normal cubic metres an hour" are not the same order of magnitude, and a quotation cannot be compared until both sides are in the same unit and at the same reference condition.
| Series | Type | Flow range | Pipe / connection | Accuracy | Power | Response | Max pressure |
|---|---|---|---|---|---|---|---|
| MF30 | Meter, MEMS, LCD | DN10 2.8–280 L/min DN15 6–600 L/min DN20 10–1000 L/min | G3/8, G1/2, G3/4 external | ±(2.0+0.2FS)% | DC12–24 V / 100 mA | 50–1000 ms | ≤1.6 MPa |
| MF50 | Meter, MEMS, integral or split | DN8 1.8–180 L/min DN10 2.8–280 DN15 6–600 DN20 10–1000 DN25 20–2000 DN32 30–3000 L/min | PT internal, DN8–DN32 | ±(1.5+0.2FS)% | DC12–24 V / 100 mA | 50–1000 ms | ≤1.6 MPa |
| MF51 | Meter, platinum resistance sensor, stainless sleeve | DN20 0.6–60 Nm³/h DN25 1–100 DN32 1.6–160 DN40 2.4–240 Nm³/h | G3/4 to G1-1/2 internal | ±(1.5+0.2FS)% | DC24 V / 1 A | 1–5 s (guide) 1 s (manual) | ≤1.6 MPa |
| MF52 | Meter, micro flow | S0 1–100 NmL/min S1 1–1000 NmL/min S2 1–100 NL/min S3 5–500 NL/min S4 10–1000 NL/min | G1/4, PT1/2 internal; adapters | <100 NL/min: ±(1.0+0.4FS)% >100 NL/min: ±(1.5+0.2FS)% | DC12–24 V / 100 mA | 50 ms warm-up 3–4 min | ≤1.0 MPa |
| MF60 | Controller, normally-closed valve | S0 1–100 SCCM … S8 3–300 SLPM | G1/4, PT1/2 internal | Control ±1.0% SP Measure ±1.0% FS (≤50 L/min), ±1.5% FS (>50 L/min) | DC12–24 V / 6 W | Control <1.5 s (T90) Measure <50 ms | Measure 0–1.5 MPa |
| MF61 | Controller, servo-motor valve, normally closed | DN10 15–300 NL/min DN15 25–500 DN20 50–1000 DN25 100–2000 DN32 150–3000 NL/min | BSPT3/8 to BSPT1-1/4 internal | Control ±1.0% SP Measure 1.5% FS (<1000 L/min) 2.0% FS (>1000 L/min) | DC12–24 V / 2.5 W | Control <20 s (T90) Measure <200 ms | Measure 0–1.5 MPa Control 0–1.0 MPa |
Two rows deserve a second look. MF51 draws 1 A at 24 V while MF30, MF50 and MF52 draw 100 mA at 12–24 V. If a panel supplies several of these from one small DC rail sized for the 100 mA family, MF51 will brown out. And MF51's response time is 1–5 seconds, not milliseconds — it is a thermal meter for larger gas lines, not a fast-response instrument.
Every range in the selection guide is measured on air at 25 ℃ and 101.32 kPa. The manual states this twice per series, and then gives a conversion table for ten gases.
| Gas | Code | Conversion factor | Range as % of air figure |
|---|---|---|---|
| Air | A | 1.0 | 100% |
| Oxygen | B | 0.9861 | 98.61% |
| Nitrogen | C | 0.994 | 99.4% |
| Argon | D | 1.4066 | 140.66% |
| Nitric oxide | E | 0.9702 | 97.02% |
| Nitrogen dioxide | F | 0.7366 | 73.66% |
| Carbon dioxide | G | 0.7326 | 73.26% |
| Methane | H | 0.7147 | 71.47% |
| Ethane | I | 0.4781 | 47.81% |
| Propane | J | 0.3459 | 34.59% |
Read the last column as the usable span on that gas relative to the air-calibrated figure. An MF50 DN20 is specified 10–1000 L/min on air. On propane, 34.59% of range means roughly 3.5–346 L/min. The instrument is not faulty and nothing needs recalibrating — but a line running at 600 L/min of propane will read over-range on a meter that looked comfortably sized on paper.
Two consequences follow, and both belong in the enquiry.
On the MF30 the factor is also a menu parameter rather than only a factory setting: F12, gas correction factor, default 1000 meaning 1.0. That exists so a meter already in service can be moved to another gas — but it corrects the reading, it does not change the sensor's usable span. A meter rescaled in the menu to propane still has the same physical range it had on air.
Argon is the useful counter-example. At 1.4066 it spans 140% of the air figure, so an argon line will read comfortably inside a meter that looked marginal on paper. Both directions of error are covered by the same table.
MF60 and MF61 are mass flow controllers. The manual lists a normally-closed valve, a control accuracy of ±1.0% SP, an input signal for the setpoint, and a response time quoted separately for control (<1.5 s, T90) and measurement (<50 ms). The others have none of that — they measure and output, and a separate valve or controller has to do the regulating.
Choosing between the two controllers comes down to one line in the two manuals, and the two lines are almost opposite.
| MF60 | MF61 | |
|---|---|---|
| Working differential pressure | 0.1–0.7 MPa (50 SLPM range); 0.1–0.6 MPa at 100 SLPM; 0.1–0.4 MPa at 300 SLPM | No pressure difference required |
| Control response | <1.5 s (T90) | <20 s (T90) |
| Turndown ratio | 1:100 | 1:20 |
| Power | DC12–24 V / 6 W | DC12–24 V / 2.5 W |
MF60 is a fast controller that lives on a regulated supply: it needs at least 0.1 MPa across the valve to have something to regulate against, and it will not hold setpoint on a 30 kPa house line however the electronics are configured. It rewards that requirement with a 1.5-second control response and a 1:100 turndown ratio.
MF61 is the opposite trade. The manual states plainly that no pressure difference is required, so it can sit on a low-pressure line where MF60 cannot — at the cost of a 20-second control response and a 1:20 turndown ratio. For a slow purge, a blanketing flow or a steady process feed, that is entirely adequate. For leak testing or fast dosing, it is not.
A mass flow controller installed on the wrong side of this table will either fail to hold setpoint or be far slower than the process expects. Both are piping and process decisions, and both need answering before the order.
Both controllers also carry a stated IP40 rating and a selectable reference temperature — 0 ℃, 20 ℃ or 25 ℃, default 25 ℃. If the contract states normal conditions at 0 ℃, that digit has to be set at the factory, not converted later.
The MF52 entry is the clearest example of why a single accuracy figure is misleading. The manual splits it at 100 NL/min:
So the same series is a higher-accuracy instrument in its lower range and a standard one above it. If a quotation quotes one number for MF52 without saying which segment, the number is not comparable.
The same logic explains why two suppliers quote different prices for what looks like the same meter at the same size. A DN20 at 10 L/min could be an MF30 at ±(2.0+0.2FS)% or an MF50 at ±(1.5+0.2FS)% — same pipe, same flow, different sensor family and different price. Accuracy class is a specification decision, not a marketing claim.
The MF30 manual shows both horizontal and vertical installation as acceptable, and then sets the straight run by what sits upstream. The figures are in pipe diameters:
| Upstream condition | Straight run before the meter (a) | Straight run after (b) |
|---|---|---|
| Reducing or expanding pipe diameter | 20 × DN | 5 × DN |
| One 90° elbow or tee | 20 × DN | 5 × DN |
| Two 90° elbows in the same plane | 25 × DN | 5 × DN |
| Two 90° elbows out of plane | 40 × DN | 5 × DN |
| Control valve upstream | 55 × DN | 5 × DN |
The manual adds one instruction that is easy to lose in a P&ID: install the control valve and the buffer cut-off valve downstream of the meter, not upstream. A regulator immediately before the sensor puts the disturbance right where the straight run is supposed to be.
These figures are from the MF30 manual. The proportion is the same physics across the series, but if the straight run is tight, check the multiplier in the manual for the model you are buying rather than applying 20 × DN by assumption.
Three exclusions appear in the MF51 manual and apply to the family as a whole. They are worth filtering an enquiry on, because each one ends a project that looked fine on a flow range.
The same series can leave the factory with different connectors, and the pin assignments are not interchangeable between them. This is the one part of the specification that must be read off the terminal label rather than copied from a table.
| Series | Connector documented | Pin assignment and source |
|---|---|---|
| MF30 | 4-core aviation cable | MF30 manual §6: 1 red 24 V+, 2 black 24 V−, 3 white I+ / RS485 A, 4 green I− / RS485 B. The selection guide lists a 6-core plug instead — see the discrepancy section below. |
| MF50 | M8 6-core, or Gx16 6-core | MF50 manual §6 gives two different pinouts. Gx16: 1 red 24 V+, 2 black 24 V− / I−, 3 green alarm output (PNP), 4 brown I+, 5 white RS485 B, 6 yellow RS485 A. M8: 1 pink 24 V− / I−, 2 black I+, 3 blue shell ground, 4 white 24 V+, 5 brown RS485 A, 6 grey RS485 B. |
| MF51 | 6-core aviation plug | Selection guide: 1 red 24 V+, 2 green pulse or PNP, 3 yellow RS485 A, 4 black 24 V− / I−, 5 brown I+, 6 white RS485 B. |
| MF61 | DB9, 9-core | Selection guide: green supply +, blue supply −, yellow 4–20 mA I+, black 4–20 mA I−, red RS485 A, brown RS485 B. |
| MF52 | Aviation socket; 4-pin micro USB on some sizes | 4-pin lead: red 24 V+, black 24 V−, white I+ / RS485 A, green I− / RS485 B. |
The comparison table above follows the Chinese selection guide, because that is the document a quotation is built from. The individual English manuals do not always match it. These are the conflicts an engineer should settle before ordering, not after:
| Item | Selection guide | Series manual |
|---|---|---|
| MF30 connector | 6-core aviation plug | 4-core aviation cable (§6) |
| MF51 response time | 1–5 s | 1 s (§3.2) |
| MF51 working pressure | ≤1.6 MPa | ≤3.0 MPa (§3.2) |
| MF51 protection | not stated | IP64 (§3.2) |
| MF51 accuracy | ±(1.5+0.2FS)% | ±1–2.5% (§3.2) |
| MF51 storage temperature | −10 to 65 ℃ | −40 to 80 ℃ (§2.2) |
| MF51 DN20 range | table 0.6–60 Nm³/h | worked example 0.5–50 Nm³/h |
None of these is a rounding difference, and two of them change what the instrument can be used for: a 3.0 MPa rating instead of 1.6 MPa, and a sensor range of −40 to 250 ℃ instead of an ambient −10 to 55 ℃. The MF51 manual separates sensor and converter temperature — sensor −40 to +250 ℃, converter −20 to +55 ℃ — while the selection guide prints a single operating range.
Where the two disagree, the manual shipped with the unit governs. For a quotation, ask which document the certificate and the nameplate follow. Publishing a comparison that silently mixes the two is how a meter arrives rated for 1.6 MPa on a 2.5 MPa line.
The instruction manuals are separate documents per series, and the pin tables and dimension drawings differ between them. Match the document to the model code before wiring:
| Series | Manual | Key content that differs |
|---|---|---|
| MF30 | MF30 Series Instruction Manual | G-thread connections, 6-pin aviation wiring, DN10–DN20 dimensions |
| MF50 | MF50 Series Instruction Manual | Integral/split options, four display orientations, DN8–DN32 dimensions |
| MF51 | MF51 Series Instruction Manual | Nm³/h ranges, 24 V/1 A supply, 1–5 s response, pulse output option |
| MF52 | MF52 Series Instruction Manual | NmL/min ranges, warm-up time, thread adapters (compression, quick-connect, hose barb) |
| MF60 | MF60 Series Instruction Manual | Valve control, differential pressure window, IP40, selectable reference temperature |
| MF61 | MF61 Series Instruction Manual | BSPT connections, DB9 wiring, shared RS485 input/output |
Send these seven items and the model code assembles itself:
Accuracy and size range. MF30 is ±(2.0+0.2FS)% with external G threads on DN10–DN20. MF50 is ±(1.5+0.2FS)%, covers DN8–DN32, and offers integral or split construction with four display orientations. For the same pipe size, MF50 is the tighter instrument.
Yes, within the converted span. Propane's factor is 0.3459, so the usable range is about 34.6% of the air figure. Size the meter on the converted range, and order the gas code in the model number rather than relying on a field conversion.
Both control. They contain a normally-closed valve and accept a setpoint through 4–20 mA, 1–5 V, 0–5 V, 0–10 V or Modbus, with a stated control accuracy of ±1.0% SP on MF60. MF30, MF50, MF51 and MF52 are meters only.
It is a different sensing construction for larger gas lines — a platinum resistance sensor in a stainless protective sleeve, with a 1–5 s response. Plan a dedicated supply rather than sharing a rail sized for the 100 mA family.
On the 4-pin lead, no — the manual states they are either/or. On the 6-core connectors (MF50, MF51) and the DB9 (MF61), both are wired separately and can be used together. MF30 depends on which connector is fitted — its own manual documents a 4-core cable, where the two are mutually exclusive.
The manual gives a 3–4 minute warm-up. Readings taken immediately after power-up are not yet at the stated accuracy.
It depends on the document. The MF51 manual states IP64 and the MF60 and MF61 documents state IP40. The selection guide lists no protection rating for MF30, MF50 or MF52 — that is not the same as an IP40 rating, so for a washdown or outdoor location ask for the enclosure specification of the exact model rather than assuming.
MF50 uses 1000, stated in its manual under the password entry section. MF30 uses 11111 — a five-digit default that can be changed in menu F91. The two are different, and an installer who has only seen one of the manuals will lock themselves out of the other.
Whatever the contract or the process data sheet uses. MF60 allows 0 ℃, 20 ℃ or 25 ℃ with 25 ℃ as the default, and the choice changes the numbers by several percent — the same reason normal and standard cubic metres are not interchangeable.
Send the gas, the flow range in your unit, the reference condition and the line pressure. Those four determine the series, the size and the calibration digit, and they are also what turns a quotation into something you can compare against another supplier's.