Anhui Jujie Automation Technology Co., LTD.
Anhui Jujie Automation Technology Co., LTD.

F3000X (GT30XF) Flow Totalizer: Manual, Specs and Setup

Table of Content [Hide]

    Short answer: the F3000X is a panel-mount flow totalizer, not a sensor. It takes the signal from a flow transmitter - 4-20 mA, 0-10 mA, frequency, or a differential pressure transmitter - applies density compensation for gas, steam or natural gas, and produces flow rate, total, shift reports and relay alarms. This page condenses the 23-page manual into the tables you actually use at the panel: terminals, equations, compensation modes, parameter map and faults.

    GT30XF F3000X flow totalizer, front panel

    The nameplate on the instrument reads F3000X; the same unit is catalogued on this site as the GT30XF flow totalizer. The manual, the product page and this page describe one product, and spare parts are ordered by either code.

    One thing worth stating before the tables: the quoted accuracy is the accuracy of the indicator, not of the flowmeter it is connected to. A Class 1.0 sensor fed into the F3000X is still a Class 1.0 measurement; the totalizer will not improve it, and the 0.2% figure only describes how faithfully the instrument reads its own input.

    What the F3000X Does and Does Not Do

    The instrument is built on an ARM Cortex-M3 core with a 128x64 monochrome LCD. It collects flow, temperature and pressure, computes the compensated result, displays four alternative screens (overview, parametric, bar-graph, signal debugging), and keeps shift, daily, monthly and annual totals. It also logs power-off events and alarms, and exports reports to a USB stick.

    It is not a flow sensor, and it is not an explosion-proof instrument: the manual states it is prohibited in flammable or corrosive atmospheres, and it is intended for indoor panel mounting with 0-50 C ambient. If you need a field-mounted Ex-rated version, the sensor side has to be specified separately.

    Specifications

    ItemValue
    Display128x64 monochrome LCD
    Accuracy (indicator)plus or minus 0.2% F.S.
    ProcessorARM Cortex-M3, 32-bit
    Flow input0-10 mA, 4-20 mA, frequency 0-5000 Hz (Vil 1 V max, Vih 5 V min)
    Temperature input0-10 mA, 4-20 mA, Pt100
    Pressure input0-10 mA, 4-20 mA
    Sensor supply1 x 12 VDC (F12) and 2 x 24 VDC (Q24, P24), 30 mA max per channel
    Current output1 channel, 4-20 mA, load 500 ohm max
    Relay outputup to 3, 3 A at 250 VAC or 3 A at 30 VDC, HH / HI / LO / LL
    CommunicationRS485 and RS232C, Modbus RTU; RS232C print port
    Report backupUSB 1.1 / 2.0, 1-32 GB stick
    Power supply220 VAC 50 Hz; 24 VDC (18-36 V) or 12 VDC (9-18 V) on order
    Clock errorplus or minus 2 s per day
    Ambient0-50 C, 0-85% RH, altitude below 2000 m
    Net weight1.0 kg or less

    Panel Cutout and Mounting

    Bezel is 160 x 80 mm; the opening is 152 x 76 mm with a +1/0 mm tolerance. Panel thickness has to be between 1.5 and 6.5 mm. The meter is pushed through from the front, then held by two brackets with M4 screws, one on each side.

    Two practical notes from the drawing: the minimum spacing between adjacent meters is set by heat dissipation, so do not butt them against each other in a dense panel; and the depth dimension on the manual drawing is labelled 750 mm, which is almost certainly a typo for 75 mm for a 160 x 80 case - measure the unit before you cut a deep enclosure.

    Terminals

    TerminalFunction
    L/+, N/-, ground, NCAC phase and neutral, protective earth; DC positive and negative; NC spare
    A+, B-RS485 communication
    R1~R2Relay outputs, 3 A at 250 VAC / 3 A at 30 VDC
    F+, F-, F12Frequency flow input, with 12 VDC feed for the sensor
    Q+, Q-, Q24Differential pressure transmitter input, with 24 VDC feed
    AO+, AO-Transmission current output
    TA, TB, TCTemperature channel (Pt100 three-wire or transmitter)
    P+, P-, P24Pressure transmitter input, with 24 VDC feed
    COMRS232C / printer (pin 2 RXD, pin 3 TXD, pin 5 signal ground)
    LANEthernet RJ45

    F3000X terminal wiring diagram

    Four wiring rules carry most of the field failures: run the measuring circuit and the power circuit in separate trays; use shielded cable where electrostatic interference is present; keep each Pt100 lead under 10 ohm with all three leads equal; and never parallel a current signal or a thermal resistance with another instrument - the reading of both units will shift.

    Flow Equations

    ModeEquationUse it with
    DP (differential pressure)Q = K x square root of (dP x density)Orifice, Venturi, averaging pitot, wedge
    Freque (frequency)Q = 3600 x If x density / KTurbine, vortex, positive displacement with pulse output
    Linear (analog)Q = K x density x dPElectromagnetic, ultrasonic, thermal mass with 4-20 mA

    The mode decides what K means, and this is where most commissioning errors start. In frequency mode K is pulses per cubic metre taken from the sensor certificate; in DP mode it is the flow coefficient derived from the orifice bore, and the square-root extraction is applied locally unless the transmitter already does it.

    Medium Compensation

    SettingWhat it doesOutput
    DisCompNo compensation; density fixed at 1000 kg/m3Volume at line conditions
    GASIdeal gas law, converts to standard conditionStandard volume
    SHSSaturated steam density from pressure or temperatureMass flow
    STSSuperheated steam density from pressure and temperatureMass flow
    NatgasIdeal gas law with compressibility factors Zn and ZfStandard volume

    For GAS and Natgas the instrument uses a reference temperature of 20.00 C and a reference pressure of 0.000 MPa gauge. That single setting decides what the word normal means on your reports: a site that contracts at 0 C will show roughly 6.8% less volume for the same mass flow, so agree the reference condition before the first invoice, not after.

    Steam modes work from the built-in steam table: SHS looks up density from pressure or temperature, STS needs both. If you are totalizing steam for cost allocation, the dryness assumption is the larger error source than the totalizer - see our steam flow meter selection guide.

    Parameter Map

    MenuWhat sits inside
    SysTime, password, cycle time, atmospheric pressure, system maintenance (clear power-off list, clear alarm list, restore defaults)
    FlowMode, unit, range, K factor, filter time, low cut, medium and compensation, cumulative unit, shift start and duration, cumulative preset, clear
    Temp / PresExternal or fixed value; Pt100 or 4-20 mA; range and offset
    OutputCurrent output type, direct or reverse action, range, signal source channel
    ALMHH, HI, LO, LL thresholds, relay assignment, dead band, cumulative alarm
    CommPC or printer mode, address 1-255, baud rate, parity, stop bits

    Login, Keys and the One Setting to Change First

    Hold Menu and Enter together for about one second to reach the configuration screen. The default password is 00 00 00 for both operator and administrator levels. Change it on day one: the same password unlocks the K factor, the compensation mode and the totals, and there is no separate audit trail for parameter edits.

    Also treat system maintenance as destructive: clearing the power-off list or restoring factory defaults wipes historical data, the alarm list and the totals, and the action cannot be undone.

    Communication

    RS485 uses A+ and B- with G for signal ground, 120 ohm termination at both ends of the bus, addresses from 1 to 255 and no duplicates. Defaults are odd parity and 2 stop bits, which is the opposite of what many PLC projects assume - check parity before you conclude the converter is faulty.

    Baud rate is stated three different ways in the manual: the specification chapter lists 1200, 2400, 4800 and 9600; the communication chapter lists 1200, 4800 and 9600; the configuration screen in the illustration shows 19200. Read the value the actual unit displays rather than the value in the PDF.

    Reports and USB Backup

    Shift, daily, monthly and annual totals are kept separately, with a configurable shift start between 0 and 11 o'clock and a shift length of 8 or 12 hours. Reports export to a FAT32 USB stick of 1 to 32 GB. If the file is empty, the usual cause is a record interval longer than the period you selected, or a stick formatted as NTFS.

    Fault Table

    SymptomCauseAction
    No powerPoor contact at the power terminal, switch not closedCheck supply and terminal screws
    Display does not match the processSignal type set wrongly, wiring errorCheck configuration against the transmitter, then the signal line
    Relay acts at the wrong pointAlarm threshold or relay assignment wrong; points shared between channelsReset threshold, remove shared assignments
    Sensor supply problemToo many transmitters drawing from the internal supply, digital and analog interferenceUse an external stabilised supply, separate the supplies
    USB transfer failsWrong start or end time, wrong format, incompatible stick, full stickSet the time range, format FAT32, use a compatible stick
    USB file empty or abnormalNo data in the selected period, system time changed, record interval too longSelect a period with data, keep the time stable, shorten the interval
    Current output wrongSignal source or range mismatchCheck the source channel and the 4-20 mA range

    Packing List

    One totalizer, two mounting brackets with M4 screws, one printed manual, one quality certificate and warranty card. The RS232C/RS485 conversion module and the RS232C cable are optional items and are not in the box unless ordered.

    FAQ

    Does the F3000X power the transmitter?
    Yes. It provides one 12 VDC output (F12) and two 24 VDC outputs (Q24, P24), each limited to 30 mA. That is enough for a standard two-wire transmitter and not enough for a loop-powered device with a heater, a display backlight or a second output; above that, feed the sensor from an external supply and use the terminals for signal only.

    Can it totalize steam?
    Yes, in SHS or STS mode, and the output becomes mass flow rather than volume. You need a working pressure or temperature input, because the density comes from the steam table rather than from a fixed value.

    Is 0.2% the accuracy of the measurement?
    No. It is the accuracy of the indicator reading its own input. The measurement accuracy is set by the flow sensor and by how well K matches the actual pipe and medium.

    Can I connect an electromagnetic flowmeter to it?
    Yes, in Linear mode with a 4-20 mA input. The totalizer then adds compensation, totals, reports and alarms to a meter that already outputs volume.

    Why does my total differ from the PLC total?
    Three usual reasons: a different reference condition for normal volume, a different low-flow cut-off, or a different K factor rounding. Compare the reference temperature and the cut percentage first.

    Does it support Modbus RTU?
    Yes, over RS485 or RS232C, with addresses 1 to 255. Set the same baud rate and parity on both sides - the factory defaults are not the most common PLC defaults.

    Download and Next Step

    The full 23-page manual, including the dimension drawing and the wiring schematic, is available as a PDF: F3000X Flow Totalizer Manual (PDF).

    The instrument itself, with the ordering code and the panel-mount options, is on the GT30XF flow totalizer product page. If the totalizer is being specified with a sensor, the matching pages are the vortex flow meters with temperature and pressure compensation and the steam flow meter selection guide. Send us the sensor certificate, the medium and the reference condition, and we will return a parameter list for the panel.

    Ethan Liu
    Ethan Liu

    Ethan Liu is JUJEA's technical content specialist, translating complex sensor integration and industrial automation concepts into practical insights for engineers, system integrators, procurement professionals, and decision-makers worldwide.

    We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. Part of the tracking is necessary to ensure SEO effectiveness,
    By using this site, you agree to our use of cookies. Visit our cookie policy to learn more.
    Reject Accept